The AC contactor has the advantages of small size, light weight, long life, low power consumption, and can be combined and derived as required. It can be equipped with building block auxiliary contact groups, air delay heads, mechanical interlocking mechanisms and other accessories to form a delay contactor, Star-delta starter, and can be directly plugged into and installed with thermal overload relay to form an electromagnetic starter. The product can be installed with screws, and can also be installed with 35mm (75mm) standard rails.
CJX2 AC contactor
Main purposes and scope of application
CJX2 series AC contactors are mainly used for AC 50Hz or 60Hz, rated insulation voltage 690V, in the AC-3 use category, rated working voltage 380V rated working current to 95A power system, for remote connection And break the circuit and frequently start and control the AC motor. It can be combined with an appropriate thermal overload relay or electronic protection device to form an electromagnetic starter to protect the circuit that may be overloaded.
This product complies with: national standards GB/T14048.1, GB14048.4, GB 14048.5.
Model and meaning
Working conditions
1. Altitude: no more than 2000m;
2. Ambient temperature: -5°C~+40°C;
3. Relative humidity: no more than 50% when the maximum temperature is +40°C; the maximum relative humidity is 90% (20 ℃). Special measures must be taken for the condensation on the product due to temperature changes;
4. The installation tilt to the vertical surface should not exceed ±22.5°;
5. Pollution degree: Level 3;
6. The installation site should be free from significant shaking, impact and vibration.
Structural features
AC contactors are small in size, light in weight, long in life, and low in power consumption. They can be combined and derived as required. They can be equipped with modular auxiliary contact groups, air delay heads, mechanical interlocking mechanisms and other accessories to form delayed contacts. Starter, star-delta starter, and can be directly plugged in and installed with thermal overload relay to form an electromagnetic starter. The product can be installed with screws, and can also be installed with 35mm (75mm) standard rails.
Main technical parameters
model |
CJX2-09 |
CJX2-12 |
CJX2-18 |
CJX2-25 |
CJX2-32 |
CJX2-40 |
CJX2-50 |
CJX2-65 |
CJX2-80 |
CJX2-95 |
|||
Rated working current A |
380V |
AC-3 |
9 |
12 |
18 |
25 |
32 |
40 |
50 |
65 |
80 |
95 |
|
AC-4 |
3.5 |
5 |
7.7 |
8.5 |
12 |
18.5 |
twenty four |
28 |
37 |
44 |
|||
660V |
AC-3 |
6.6 |
8.9 |
12 |
18 |
twenty one |
34 |
39 |
42 |
49 |
55 |
||
AC-4 |
1.5 |
2 |
3.8 |
4.4 |
7.5 |
9 |
12 |
14 |
17.3 |
21.3 |
|||
Conventional heating current A |
20 |
20 |
32 |
40 |
50 |
60 |
80 |
80 |
125 |
125 |
|||
Controllable three-phase squirrel cage |
220V |
2.5 |
3 |
4 |
5.5 |
7.5 |
11 |
15 |
18.5 |
twenty two |
25 |
||
380V |
4 |
5.5 |
7.5 |
11 |
15 |
18.5 |
twenty two |
30 |
37 |
45 |
|||
660V |
5.5 |
7.5 |
9 |
15 |
18.5 |
30 |
33 |
37 |
45 |
55 |
|||
Frequent operation/n |
Electric life |
AC-3 |
1200 |
600 |
|||||||||
AC-4 |
300 |
||||||||||||
Mechanical life |
3600 |
||||||||||||
Electric life ten thousand times |
AC-3 |
|
100 |
80 |
60 |
||||||||
AC-4 |
|
20 |
15 |
10 |
|||||||||
Mechanical life ten thousand times |
|
1000 |
800 |
600 |
|||||||||
Equipped with fuse model |
RT16-20 |
RT16-20 |
RT16-32 |
RT16-32 |
RT16-50 |
RT16-63 |
RT16-80 |
RT16-80 |
RT16-100 |
RT16-125 |
|||
Standards compliant |
GB14048.1 GB14048.4 IEC60947-4-1 |
CJX2-09~18 outline and installation dimensions
CJX2-25, 32 outline and installation dimensions
CJX2-40~95 appearance and installation dimensions
model |
Amax |
Bmax |
Cmax |
C1max |
C2max |
a |
b |
c |
CJX2-09~12 |
47 |
76 |
82 |
115 |
134 |
35 |
55 |
4.5 |
CJX2-18 |
47 |
76 |
87 |
120 |
139 |
|||
CJX2-25 |
57 |
86 |
97 |
130 |
149 |
40 |
55 |
4.5 |
CJX2-32 |
57 |
86 |
102 |
135 |
154 |
|||
CJX2-40~65 |
77 |
129 |
116 |
149 |
168 |
40 |
105 |
6.5 |
CJX2-80~95 |
87 |
129 |
127 |
160 |
179 |
Note: C1max- is contactor + F4; C2max- is contactor + SK4.
Ordering instructions When
ordering, it must be pointed out:
a. The complete name and model of the contactor;
b. The rated control power voltage and frequency or code of the coil;
c. The additional F4 auxiliary contact group or standard card rail must be ordered, which should be noted separately;
d. Order quantity;
If you have any enquiry about quotation or cooperation,please free to email us ata65148373@163.comor use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.
Share our Product over the Social Networks
Search across our website